TCG-6131P Temperature Controller

TC series intelligent controller is mainly used for temperature control. across verity of industries; from food process, plastics, packaging, oven mechanic to chemical processing, power plants and refinery. This controller reveals both classic and modern control theories combining intelligent PID, auto-tuning optimization.

 

Product Highlights:

Powered by a single-chip MCU for controlling features.

Two colors, red and green; double rows of digits displaying actual and target values.

Various parameters can be key-in from front panel.

PID parameters auto tuning; Manuel preset value capability.

Alarms when Upper Limit reaches.

Alarm Offset Value setting capability.

Dedicated thermocouple (temp. sensor) included.

 

Physical Dimensions: (mm)

Depth (length) 110

Front Width 48

Front Height 48

Rear Width 43

Rear Height 43

An opening size of 45.6 x 45.6 should fit the controller installation.

 

Technical Specification:

1.         -199~999

2.         Alarm range: Can be set within the whole range.

3.         Power supply: 110VAC 50Hz 7VA Max

4.         Ambient Temperature: 50 degree C Max; relative humidity < 85%.

 

This device should be used with the dedicated thermocouple (K type) which should be used within operating range 0~1300 deg C.

 

Front Panel and Parameter setting loop.

To set Target Value

1) Power it and wait for up to 30 seconds for the controller warm up.

2)        Press SET 0.5s to enter So setting window.

3)        Press SET 0.5s again to go back to Normal window.

 

1)        Press SET over 5s to enter/exit the parameter setting loop.

2)        Parameters can be adjusted are:
       SHPScSOHP]dtAtLoK

3)        When in the parameter setting loop and no keys were pressed

for 30 seconds, it will automatically exit and parameters adjusted

will not be valid.

(To exit with adjusted value saved, press SET over 5 seconds.)

4)        When in the parameter setting loop, if At=01 is being set, press

SET over 5s to exit. Then At indicator will be on and Auto-tuning

will take effect.

5)        Everytime entering parameter setting loop, Auto-tuning will reset to At=00.

6)        To prevent other change parameters, LoK values can be set to 01 or

02 before exiting parameter setting loop.

 

1 Set Button

2 Decrement button

3 Increment button

4 Measured value display

5 Target value display

6 OUT1, Output indicator; (OUT2 indicator not used)

light on when there is output

light off when not output

7 AT, Auto tune indicator

8 ALM, Alarm output indicator (red=relay closed)

Parameter

Meaning

Value Range

Comment

Default Value

(1) So

Output Target

0~999 deg C

Set target value

150

(2) SHP

Upper Limit Offset

-20~999 deg C

Above this value the red alarm indicator turns on. Alarm relay connects closed

10

(3) SC

Thermocouple correction

-20~20

To correct offset error of conductions.

0

(4) SOH

Target Value Upper Limit

0-999

Limits target value upper limit.

20

(4) P

Proportional band

1~span

Set heating-side proportional band.

20

(5) ]

Integration time

0, 1~3600 sec

To eliminates offset occurring control. 0=Function turned off.

130

(6) d

Derivative time

0, 1~3600 sec

To prevent ripples by predicting output change thereby improving control stability. 0= Function turned off

30

(7) t

Proportional Cycle

(Heating side)

1~99 sec

Set control output cycle. Short cycle time make output become pulses.

20(2)

(8) Ar

Auto tunning

00: off

01: on

 

00

(9) LoK

Lock Setting

00: Not lock

01: Lock all but main control

02: Lock all parameters

To allow or not allow parameter change.

00

 

Make sure supply voltage of the device is met.

Exams wire for correct hook up and connections.

Try to use same length low impedance wires when connecting thermocouple.

Avoid routing high power wires near signal input wires.

Always check relays connections and wirings first when device is abnormal.